5925-00-762-1720, 5925007621720 (Circuit Breaker) - National Stock Number Lookup

NSN 5925-00-762-1720 of part number NFJ631100-50DEGC by the manufacturer, Challenger Electrical Equipment Corp is in stock and ready to ship out. We make NSN parts purchasing as simple as possible. We list corresponding components such as 5925-00-762-1720 so that you can make the purchasing decision that is right for you. Our dedicated team are on hand to help source any-hard-find NSN parts or answer any procurement questions. We only source from manufacturers we trust and are the only independent distributor with a NO CHINA SOURCING policy. Unlike other companies, we pair every customer with a dedicated account manager. We respond to all RFQs within 15 minutes. Submit an RFQ today to get started.

5925-00-762-1720 NSN Information

Alternative NSN: 5925-00-762-1720
Item Name: Circuit Breaker
FSG: 59 Electrical and Electronic Equipment Components
Federal Supply Class (FSC): 5925 Circuit Breakers
NIIN: 007621720
NCB Code: USA (00)
Manufacturers: Challenger Electrical Equipment Corp

NSN 5925-00-762-1720 Manufacturing Part Numbers

Part No Manufacturer Item Name QTY RFQ
NFJ631100-50DEGC challenger electrical equipment corp circuit breaker Avl RFQ

Product Specification of NSN 5925007621720

MRCCriteriaCharacteristic
AAQLBODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
ADAQBODY LENGTH9.500 INCHES NOMINAL
ADATBODY WIDTH4.125 INCHES NOMINAL
ADAUBODY HEIGHT4.062 INCHES NOMINAL
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH8.000 INCHES NOMINAL
AEBVUNTHREADED MOUNTING HOLE DIAMETER0.218 INCHES NOMINAL
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH7.250 INCHES NOMINAL
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.375 INCHES NOMINAL
AJECBOSS HEIGHT0.250 INCHES NOMINAL
AKPXPOLE QUANTITY3
AXHRMOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE100.0 AMPERES AC ALL LOCATIONS
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC ALL LOCATIONS
CPRHCIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
CPRJTRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
CPRLTRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT70.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 160.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CRCFTRIP RELEASE AMBIENT TEMP RATING50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
FREQFREQUENCY IN HERTZ60.0 ALL LOCATIONS
ADTVCASE MATERIALPLASTIC
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.375 INCHES NOMINAL
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC ALL LOCATIONS
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
TTQYTERMINAL TYPE AND QUANTITY6 COMPRESSION

NSN 5925-00-762-1720 - Similar National Stock Numbers

Get an Estimate for Your Required Component

You will receive a response in 15 minutes or less









Install ASAP App for Quick Actions